Details On The Control Circuit Terminals (Safety Communication Model) - Mitsubishi Electric 800 Series Instruction Manual

575v class, compact, high functionality inverters, 0.75k-7.5k
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

2.6.3
Details on the control circuit terminals (Safety
communication model)
 Input signal
Terminal
Type
Terminal name
symbol
Frequency setting
10
power supply
Frequency setting
2
(voltage)
Frequency setting
4
(current)
Frequency setting
5
common
*1
Refer to the FR-E800 Instruction Manual (Function).
 Output signal
Terminal
Type
Terminal name
symbol
A,
Relay output (fault
B,
output)
*1
C
*1
The terminal function can be selected by Pr.192 (Output terminal function selection). (Refer to the FR-E800 Instruction Manual (Function).)
*2
Refer to the FR-E800 Instruction Manual (Function).
Terminal function description
Used as the power supply for an external frequency setting
(speed setting) potentiometer.
Inputting 0 to 5 VDC (or 0 to 10 VDC) provides the maximum
output frequency at 5 V (or 10 V) and makes input and
output proportional. Use Pr.73 to switch among input 0 to 5
VDC (initial setting), 0 to 10 VDC, and 0 to 20 mA.
* The initial setting varies depending on the specification.
Set the voltage/current input switch to the "I" position to
select current input (0 to 20 mA).
Inputting 4 to 20 mADC (or 0 to 5 VDC, 0 to 10 VDC)
provides the maximum output frequency at 20 mA and
makes input and output proportional. This input signal is
valid only when the AU signal is ON (terminal 2 input is
invalid).
To use terminal 4 (current input at initial setting), assign "4"
to Pr.178 or Pr.189 (Input terminal function selection) before
turning ON the AU signal.
* The initial setting varies depending on the specification.
Use Pr.267 to switch among input 4 to 20 mA (initial setting),
0 to 5 VDC, and 0 to 10 VDC. Set the voltage/current input
switch to the "V" position to select voltage input (0 to 5 V / 0
to 10 V).
Common terminal for the frequency setting signal (terminal
2 or 4). Do not earth (ground).
Terminal function description
1 changeover contact output that indicates that an inverter's
protective function has been activated and the outputs are
stopped.
Fault: discontinuity across B and C (continuity across A and
C), Normal: continuity across B and C (discontinuity across
A and C)
Refer
Rated specification
to
page
5 ±0.5 VDC,
*1
permissible load current:
10 mA
*1
For voltage input,
input resistance: 10±1
kΩ, maximum permissible
voltage: 20 VDC.
For current input,
input resistance: 245 ±5
Ω, maximum permissible
current: 30 mA.
Voltage/current
input switch
*1
2
V
I
4
*1
Refer
Rated specification
to page
Contact capacity: 240
VAC 2 A
*2
(power factor = 0.4), 30
VDC 1 A
2. Installation and Wiring
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
49