The initial setting varies depending on the specification.
*4
Terminal input specifications can be changed by analog input specification switchover (Pr.73, Pr.267). To input voltage, set the voltage/current
input selection switch to "V". To input current, set the switch to "I". The initial setting varies depending on the specification. (Refer to the FR-E800
Instruction Manual (Function).)
*5
It is recommended to use 2 W 1 kΩ when the frequency setting signal is changed frequently.
*6
The function of these terminals can be changed using the Pr.192 ABC terminal function selection.
*7
The function of these terminals can be changed using the Output terminal function selection (Pr.190, Pr.191).
*8
Not required when calibrating the scale with the operation panel.
NOTE
• To prevent a malfunction due to noise, keep the signal cables 10 cm or more away from the power cables. Also, keep the
cables of the main circuit for input and output separated.
• After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause a fault, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the inverter.
• Set the switches of the voltage/current input selection switch assembly correctly. Incorrect setting may cause a fault, failure or
malfunction.
34
2. Installation and Wiring
2.4 Terminal connection diagrams