Connection Configuration In The Cp1430 Tcp (Simatic S5) - Siemens SIMATIC S5 Manual

Ethernet communication (iso on tcp) between controllers
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

2 Engineering
6
7
2.5.5

Connection configuration in the CP1430 TCP (SIMATIC S5)

Introduction
The following settings are used to establish a "passive" ISO-on-TCP DUPLEX
connection to the CP1543-1.
The CP1430 TCP configuration file "TCP1430A.TCP" already contains the
Note
complete configurations for all 7 example scenarios. Thus, after loading the
CP1430 file, all other connections are also available "offline" in the CP1430 TCP.
Configuration
The "passive" connection for scenario 3 in the CP1430 TCP is created using the
"SINEC NCM COM 1430 TCP" configuration tool.
The "SINEC NCM COM 1430" configuration tool is an additional software that is
Note
integrated in STEP 5 to configure the CP1430 TCP. This software is not included
in the standard STEP 5 package and must be installed additionally.
The connection configuration is largely identical to chapter 2.2.5. Follow the steps 1
to 8 described in that chapter and complete the configuration following the steps
described below.
9.
For this example, two ISO-on-TCP connections (transport connections RFC
1006) are required.
To set up the "passive" connection, the job "1 of 2" must be parameterized as
a RECEIVE type. In the subsequent mask of the job, the TSAP "CP1543-2"
has to be entered. The job "2 of 2" must be set up as a SEND job type.
Ethernet Communication (ISO on TCP) between SIMATIC S5 and
SIMATIC S7-1500 Controllers
Entry-ID: 109482475,
V1.2,
07/2019
57

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic s7-1500Cp1543-1Cp1430 tcp

Table of Contents