Scenario 2B - Communication Via Programmed Ouc (Single Instructions) And Internal Cpu Interface; Mode Of Operation - Siemens SIMATIC S5 Manual

Ethernet communication (iso on tcp) between controllers
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

2 Engineering
Scenario 2b – Communication via programmed OUC
2.4
(single instructions) and internal CPU interface
2.4.1

Mode of operation

Overview
In this scenario, the SIMATIC S5 actively establishes an ISO-on-TCP connection
to the S7-1500 CPU via the CP1430 TCP using the internal PROFINET interface.
On the S7-1500 CPU end, the programmed connection is set up passively via the
OUC block TCON by the user program and is available for establishing the
connection of the partner. The data then are sent and received via the blocks
TSEND and TRCV.
For this connection, the SIMATIC S5 uses the standard handling blocks
SYNCHRON/SEND/RECEIVE. In the CP1430 TCP, the ISO-on-TCP connection in
the SIMATIC S5 is configured as an "active" duplex connection.
Flow chart
Sequence of the programmed OUC communication between S7 and S5 via single
instructions
The figure below schematically shows the connection established and the data flow
between SIMATIC S5 and SIMATIC S7-1500 using the SEND and RECEIVE
mechanism via ISO-on-TCP.
SIMATIC S5 CPU
OB1
FB40
RECEIVE
RECEIVE
Ethernet Communication (ISO on TCP) between SIMATIC S5 and
SIMATIC S7-1500 Controllers
Entry-ID: 109482475,
V1.2,
1
HTB
SYNCRON
SEND
SEND job trigger
HTB
SEND
4
SEND
ALL
Value 1
Value 2
...
...
...
RECEIVE
3
HTB
Value 1
Value 2
...
...
ALL
...
07/2019
SIMATIC S7-1500 CPU
Conn. establ./
CP1430
CPU 1500
disconn.
TCP
PNIO SS
2
CR
Connection
Connection
configuration
CC
A_NR
TSAP 1
SEND/RCV
...
Acknowledgment
Data
Acknowledgment
Data
OB1
CONNECT
Connect
TCON
conn.
passive
ID 5
TSAP 1
TDISCON
5
RECEIVE
TRCV
Value 1
Value 2
...
6
SEND
TSEND
Value 1
Value 2
...
43