Ethernet communication (iso on tcp) between controllers
Hide thumbs Also See for SIMATIC S5:
Table of Contents

Advertisement

2 Engineering
Scenario 5 – Communication via programmed OUC (compact
2.10.7
instructions) and internal CPU interface
Prerequisite
PLC_Sz5_S-R_CPU_TSEND_C_ID6
Activate the corresponding enable bit in the SIMATIC S5-CPU via the "BB1" watch
table.
For scenario 5, the corresponding S7-1500 program can be activated via the
enable bit E 0.1.
Now, the connection will be established by the SIMATIC S7 station.
Test and diagnostics of communication in the SIMATIC S7-1500
The bidirectional data exchange (continuous count value) can be monitored via the
output byte (AB0) of the S7-1500.
To monitor the ongoing communication and the status of the send and receive
blocks in the SIMATIC S7-1500, call the watch table "BEO_Sz5_ID6" in TIA Portal.
There, you can monitor the last error status displays of the OUC blocks TSEND_C
(1) and TRCV (2).
If the TSEND_C instruction has been executed successfully or with errors, the
status of the TSEND_C instruction will be stored in the
"DB_FC_SEND".STATUS_SAVE variable. The status provides information on the
reason why the send job is not running.
Ethernet Communication (ISO on TCP) between SIMATIC S5 and
SIMATIC S7-1500 Controllers
Entry-ID: 109482475,
V1.2,
Loaded
S7-1500 station
1
2
07/2019
Enable bit S7-1500
CPU for scenario 4b
E 0.1
Activated enable bit
(S5-CPU)
M 130.6
104