On-Board Single-Pole 2 A Outputs/Test Pulses - Pilz PSS Series Installation Manual

Programmable safety systems
Hide thumbs Also See for PSS Series:
Table of Contents

Advertisement

Connecting the Inputs and Outputs

On-board single-pole 2 A outputs/test pulses

Number
Configuration O1.0 - O1.15
Features:
• The outputs are push-pull outputs. Do not use the push-pull level to drive
a load to L-, otherwise the switch off test will detect a connection to L+ and
will register an error.
• The outputs can be configured as test pulse outputs or single-pole 2 A
outputs in groups of 8 (standard PSS 3056, PSS 3056-1 and PSS SB
3056) or 4 (PSS 3056-2). The following configuration is set automatically,
depending on the number of test pulses configured in the programming
device:
Standard PSS 3056, PSS 3056-1 and PSS SB 3056:
Number < 8: O1.00 ... O1.07 are test pulse outputs
Number > 8: O1.00 ... O1.15 are test pulse outputs
Number = 0: O1.00 ... O1.15 are single-pole 2 A outputs
PSS 3056-2:
Number < 4: O1.00 ... O1.03 are test pulse outputs
Number > 4: O1.00 ... O1.03 and O1.08 ... O1.11 are test pulse outputs
Number = 0: O1.00 ... O1.03 and O1.08 ... O1.11 are single-pole 2 A
• Two adjacent inputs must not be connected to the same test pulse.
NOTICE
When using single-pole outputs, always ensure that line or cable breaks
and short circuits between lines can always be detected, or ensure they
cannot occur by using appropriate wiring.
• Outputs configured as 2 A outputs have monitoring inputs available
under the same address. These can be used for feasibility checks.
• If cable runs are greater than 200 m with a cable cross section of
1.5 mm
of 2.5 mm
• If cable runs are greater than 800 m, interference from switching
operations in 24 VDC signals may affect the test pulse outputs.
5-16
Artisan Scientific - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisan-scientific.com
PSS 3056
PSS SB 3056
16
O1.08 ... O1.15 are single-pole 2 A outputs
O1.08 ... O1.11 are single-pole 2 A outputs
outputs
2
, or cable runs are greater than 300 m with a cable cross section
2
, the operating system will not detect a short circuit to earth.
PSS 3056-1
PSS 3056-2
16
8
O1.0 - O1.15
O1.0 - O1.3
O1.8 - O1.11
Installation Manual: PSS 3056 Series