VLT® Micro Drive FC 51
Operating Guide
3.5.5 Recommendation of Fuses
Table 4: Fuses
FC 51
kW
1x200–240 V
0K18–0K37
0K75
1K5
2K2
3x380–480 V
0K37–0K75
1K5
2K2
3K0
4K0
5K5
7K5
11K0
15K0
18K5
22K0
3.6 Connecting to Mains and Motor
The drive is designed to operate all standard 3-phased asynchronous motors.
The drive is designed to accept mains/ motor cables with a maximum cross-section of 4 mm
maximum cross-section of 16 mm
Danfoss A/S © 2020.09
Maximum fuses non–UL
Type gG
16A
25A
35A
50A
10A
16A
20A
40A
40A
40A
40A
63A
63A
80A
80A
2
/6 AWG (M4 and M5).
Installation
2
/10 AWG (M1, M2, and M3), and a
AQ348848915086en-000101 / 130R0943 | 11
Need help?
Do you have a question about the VLT Micro Drive FC 51 and is the answer not in the manual?
Questions and answers