Setting External Face Area Input; Setting Face Area Output Range - Siemens SOAM Manual

Fume hood sash open area module, application 2957: dual bench style – dual combination with 2 to 4 horizontal sashes in the vertical carrier configuration start-up procedures.
Table of Contents

Advertisement

Before You Begin

Setting External Face Area Input

10 | 12
Siemens Industry, Inc.
Sash Panel
Vertical 1
Vertical 2
Horizontal 3
Horizontal 4
Horizontal 5
Horizontal 6
Horizontal 7
Horizontal 8
Horizontal 9
Horizontal 10
Setting External Face Area Input
Skip this section if you are only using one SOAM, leave values at default.
AI can be set up as an input for external face area.
1. Set MAX EXT AREA to the area corresponding to 10 volts from the input signal
source.
 The next step allows the minimum voltage to bet set to a value other than 1
(default). The minimum voltage is represented when the face area is equal
to 0.
2. Set MIN EXTVOLTS to the voltage corresponding to 0 face area from the input
signal source. (default = 1.0 Vdc)
 The resulting area displays in point EXTERNAL A.
NOTE:
If no external area input is be connected to the AI, make sure MAX EXT AREA =
0 (default). This disables the alarm feature that fails the FACE AREA point when
the input signal drops below 1 Vdc.

Setting Face Area Output Range

1. Set REPORT to FACE AREA OUT.
2. Set MAX FACE A to the maximum expected face area for the fume hood, plus
approximately 10%. Example: If the maximum face area is 9 sq ft, set it to 10.
 FACE A OUT is now active and a proportional 1 to 10V signal can be read
on AO. 1V equals 0 sq ft and 10V = MAX FACE A.
3. Set AO DEADBAND to the desired value.
Restricted
Sash Point/Wiring.
Point
31
32
33
34
35
36
37
38
39
40
Descriptor
POS SASH 1
POS SASH 2
POS SASH 3
POS SASH 4
POS SASH 5
POS SASH 6
POS SASH 7
POS SASH 8
POS SASH 9
POS SASH 10