Flashing Controller Firmware - Siemens SOAM Manual

Fume hood sash open area module, application 2957: dual bench style – dual combination with 2 to 4 horizontal sashes in the vertical carrier configuration start-up procedures.
Table of Contents

Advertisement

Siemens Industry, Inc.
NOTE:
AO DEADBAND can be set from 0 to 100% in 0.4% increments. 0% will give the
actual face area all the time. If a sash input signal is unstable, this will cause an
unstable reading to be sent to the output which could cause short-term instability
or control problems. Increase the values to give a stable output and remove the
signal bounce. A 10% deadband is equal to a ± 5% of the face area.
AO DEADBAND defaults to 0%. If FACE A OUT changes by less than the
percentage value in AO DEADBAND, the output will not update. Once the value
changes greater than the AO DEADBAND, the output will be updated to the
currently calculated value.
If needed, set MIN FA VOLTS (default = 1 Vdc).
MIN FA VOLTS can be left at default for most installations. Changing this value
changes the voltage output when the FACE AREA = 0 sq ft.
NOTE:
If the MIN FA VOLTS is set to 0, failure detection is lost.

Flashing Controller Firmware

WCIS Procedure
1. Connect to the USB port of the SOAM.
2. From the Device menu, select Load TEC Firmware.
 The Load TEC Firmware dialog box displays.
3. Click the Browse button.
4. Browse to the folder where the new firmware is saved.
5. Double-click the firmware file and then click Load.
Restricted
Before You Begin
Flashing Controller Firmware
A6V10801619
11 | 12
07.06.2016