External Input; Sensor Characteristics - Siemens SITRANS F M MAGFLO series Operating Manual

Modbus rtu rs-485 add-on module for usm ii transmitters
Hide thumbs Also See for SITRANS F M MAGFLO series:
Table of Contents

Advertisement

Modbus RTU RS-485

6.7 External input

6.8 Sensor characteris-
tics
6.
Modbus holding registers
MAG 6000
Modbus
Modbus
register
address
4:02301
2300
4:02302
2301
4: 02303
2302
MASS 6000
Modbus
Modbus
register
address
4:02301
2300
4:02302
2301
4: 02303
2302
MAG 6000
Modbus
Modbus
register
address
4:02401
2400
4:02403
2402
4:02405
2404
4:02421
2420
MASS 6000
Modbus
Modbus
register
address
4:02401
2400
4:02403
2402
4:02405
2404
4:02407
2406
4:02409
2408
4:02411
2410
4:02413
2412
4:02415
2414
4:02417
2416
4:02419
2418
4:02422
2421
SFIDK.PS.023.D2.02
No. of
Data
Description
bytes
type
Input Function:
2
Byte
0 = Off
1 = Start Batch
2 = Hold/Continue
3 = Stop Batch
4 = Zero Adjust
5 = Totalizer reset
6 = Force output
7 = Freeze output
8 = Qmax 2 (night)
9 = Manual cleaning
2
Byte
Totalizer reset:
0 = Totalizer 1
1 = Totalizer 2
2 = Totalizer 1 + 2
4
Float
Force output (1/100%)
No. of
Data
Description
bytes
type
Input selection:
2
Byte
0 = Off
1 = Start Batch
2 = Hold/Continue
3 = Stop Batch
4 = Zero Adjust
5 = Totalizer reset
6 = Force output
7 = Freeze output
2
Byte
Totalizer reset:
0 = Totalizer 1
1 = Totalizer 2
2 = Totalizer 1 + 2
4
Float
Force output (1/100%)
No. of
Data
Description
bytes
type
4
Float
Sensor size (m)
4
Float
Calibration factor
4
Float
Correction factor
2
Byte
Excitation frequency:
0 = 3.125 Hz (50 Hz)
1 = 6.25 Hz (50 Hz)
2 = 12.5 Hz (50 Hz)
3 = 25 Hz (50 Hz)
4 = 1.5625 Hz (50 Hz)
5 = 44 Hz (only SV)
6 = 2.0833 Hz
7 = 1.875 Hz (60 Hz)
8 = 3.75 Hz (60 Hz)
9 = 7.5 Hz (60 Hz)
10 = 15 Hz (60 Hz)
11 = 30 Hz (60 Hz)
No. of
Data
Description
bytes
type
4
Float
Sensor size (m)
4
Float
Calibration factor (us2/kg)
4
Float
Correction factor
Sensor TC (1/100% / °C)
4
Float
4
Float
Density parm. A (kg/m
4
Float
Density parm. B (*10E6)
Density TC (1/100% / °C)
4
Float
4
Float
Density offset (kg/m
4
Float
Density factor
4
Float
Table slope (kg/s)
4
Float
Fraction offset (kg/s)
Read/
write
R/W
R/W
R/W
Read/
write
R/W
R/W
R/W
Read/
write
Read/
write
R/W
R/W
R/W
R/W
3
)
R/W
R/W
R/W
3
)
R/W
R/W
R/W
R/W
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans f c massflo series