Fume hood sash open area module, application 2957: dual bench style – dual combination with 2 to 4 horizontal sashes in the vertical carrier configuration start-up procedures.
Table of Contents

Advertisement

Siemens Industry, Inc.

Sash Setup and Calibration

NOTE:
Enter all measurements to the nearest .0.25 inch (0.635 cm).
Sash Setup 2957
1.
Set REPORT to OVERVIEW.
NOTES: Numbers on the sashes show how the sash is wired. After the
physical sashes are calibrated, the position of the sashes will display in POS
SASH 1, POS SASH 2, and so on.
The horizontal sash numbering in vertical sash 2 always starts with 7. For
example, if HZ PANEL CT = 4, then vertical sash 1 contains sashes 3 and 4
and vertical sash 2 contains sashes 7 and 8.
2.
Determine the number of horizontal sash panels. This number includes the
horizontal sashes in both combination sashes. The segments must contain
the same number of horizontal sashes. Set HZ PANEL CNT to this value.
3.
Measure the width of the vertical sash 1 in inches (cm). Set VSASH
WIDTHA to this value.
4.
Measure the width of the opening in vertical sash 1 in inches (cm). Set
TRACK WIDTHA to this value.
5.
Measure the height of the opening in vertical sash 1 in inches (cm). Set
PANEL HGHTA to this value.
6.
Repeat steps 2 through 5 for vertical sash 2. Enter the values into VSASH
WIDTHB, TRACK WIDTHB and PANEL HGHTB.
7.
Measure the width of the individual sash panels in inches (cm). Choose one
of the following:
Restricted
Fume Hood Specific Sash Setup and Calibration
Nine Combination Sash Configuration.
Before You Begin
5 | 12
A6V10801619
07.06.2016