ABB REU615 Applications Manual page 60

Voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

Section 3
REU615 standard configurations
54
GUID-73D10A91-CE58-4368-9C88-39D2268580E6 V1 EN
Figure 29:
Master Trip
The operate signals from the protections are connected to the trip output contact
PO3 (X100:15-19) via the corresponding Master Trip TRPPTRC1.
TRPPTRC provides the lockout/latching function, event generation and the trip
signal duration setting. If the lockout operation mode is selected, one binary input
can be reassigned to the RST_LKOUT input of the Master Trip to enable external
reset with a push button.
GUID-E4270342-93C0-4C06-B8F2-297E24A434FE V1 EN
Figure 30:
On load tap changer control
The on load tap changer control functionality is provided with the OLATCC1
function. Both manual and automatic controlling of the on load tap changer is done
via OLATCC. The external push button controlling of the local tap changer can be
wired to binary inputs, BI3 (X110:5-6) for lower request and BI4 (X110:7-6) for
raise request. Also it is possible to set the function into parallel mode with
activating the BI5 (X110:8-9) input and to the automatic mode with BI6 (X110:10-9).
1MRS757054 A
REU615
Application Manual