Standard Configuration A; Applications - ABB REU615 Applications Manual

Voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

Section 3
REU615 standard configurations
3.4
3.4.1
28
forming principle diagrams. The external connections to primary devices are also
shown, stating the default connections to measuring transformers. The positive
measuring direction of directional protection functions is towards the outgoing feeder.
The functional diagrams are divided into sections with each section constituting
one functional entity. The external connections are also divided into sections. Only
the relevant connections for a particular functional entity are presented in each
section.
Protection function blocks are part of the functional diagram. They are identified
based on their IEC 61850 name but the IEC based symbol and the ANSI function
number are also included. Some function blocks, such as PHHPTOC, are used
several times in the configuration. To separate the blocks from each other, the IEC
61850 name, IEC symbol and ANSI function number are appended with a running
number, that is an instance number, from one upwards. If the block has no suffix
after the IEC or ANSI symbol, the function block has been used, that is,
instantiated, only once. The IED's internal functionality and the external
connections are separated with a dashed line presenting the IED's physical casing.
Signal Matrix and Application Configuration
With Signal Matrix and Application Configuration in PCM600, it is possible to
modify the standard configuration according to the actual needs. The IED is
delivered from the factory with default connections described in the functional
diagrams for binary inputs, binary outputs, function-to-function connections and
alarm LEDs. The Signal Matrix is used for GOOSE signal input engineering and
for making cross-references between the physical I/O signals and the function
blocks. The Signal Matrix tool cannot be used for adding or removing function
blocks, for example, GOOSE receive function blocks. The Application
Configuration tool is used for these kind of operations. If a function block is
removed with Application Configuration, the function related data disappears from
the menus as well as from the 61850 data model, with the exception of some basic
function blocks, which are mandatory and thus cannot be removed from the IED
configuration by removing them from the Application Configuration.

Standard configuration A

Applications

The standard configuration is intended for voltage protection and synchronism
check in medium voltage networks. The standard configuration handles fault
conditions originating from abnormal voltages in the power system. Also the
synchronism and energizing check can be handled for two galvanically
interconnected networks.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
1MRS757054 A
REU615
Application Manual