ABB REU615 Applications Manual page 19

Voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

1MRS757054 A
REU615
Application Manual
Main
Slot ID
Content options
Case
X130
AI/BI module
Optional RTD/mA module
Optional BIO module
X000
Optional communication
module
Rated values of the current and voltage inputs are basic setting parameters of the
IED. The binary input thresholds are selectable within the range 18...176 V DC by
adjusting the binary input setting parameters.
The rated input levels are selected in the IED software for phase current and
ground current. The binary input thresholds 18...176 V DC are selected by
adjusting the IED's parameter settings.
The optional BIO module can be added in the IED to all standard
configurations.
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and
the plug-in unit.
Table 3:
Number of physical connections in standard configurations
Conf.
CT
A
-
B
4
1) With optional BIO module
2) With optional RTD/mA module
Only with configuration A:
3 phase voltage inputs (60-210 V)
1 residual voltage input (60-210 V)
1 reference voltage input for SECRSYN1 (60-210 V)
4 binary inputs
Optional for configuration B:
2 generic mA inputs
6 RTD sensor inputs
Optional for configuration B:
6 binary inputs
3 signal output contacts
See technical manual for details about different
type of communication modules.
Analog channels
VT
RTD/mA
5
-
-
3
2)
6/2
Section 2
REU615 overview
Binary channels
BI
BO
12
10
1)
1)
8 (14)
10 (13)
8
10
13

Advertisement