Default I/O Connections - ABB REU615 Applications Manual

Voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

Section 3
REU615 standard configurations
3.4.2.1
30
Functionality
Load shedding and restoration,
instance 1
Load shedding and restoration,
instance 2
Load shedding and restoration,
instance 3
Load shedding and restoration,
instance 4
Load shedding and restoration,
instance 5
Control
Circuit-breaker control
Disconnector position indication,
instance 1
Disconnector position indication,
instance 2
Disconnector position indication,
instance 3
Earthing switch indication
Synchronism and energizing check
Condition monitoring
Trip circuit supervision, instance 1
Trip circuit supervision, instance 2
Measurement
Disturbance recorder
Three-phase voltage measurement
Residual voltage measurement
Sequence voltage measurement
Frequency measurement

Default I/O connections

Table 9:
Default connections for binary inputs
Binary input
Default usage
X110-BI1
Setting group change
X110-BI2
Manual restore group 1
X110-BI3
Manual restore group 2
X110-BI4
X110-BI5
Voltage transformer truck in indication
X110-BI6
Voltage transformer truck out indication
X110-BI7
Earth switch closed indication
X110-BI8
Earth switch open indication
Table continues on next page
IEC 61850
IEC 60617
LSHDPFRQ1
UFLS/R (1)
LSHDPFRQ2
UFLS/R (2)
LSHDPFRQ3
UFLS/R (3)
LSHDPFRQ4
UFLS/R (4)
LSHDPFRQ5
UFLS/R (5)
CBXCBR1
I <-> O CB
DCSXSWI1
I <-> O DC (1)
DCSXSWI2
I <-> O DC (2)
DCSXSWI3
I <-> O DC (3)
ESSXSWI1
I <-> O ES
SECRSYN1
SYNC
TCSSCBR1
TCS (1)
TCSSCBR2
TCS (2)
RDRE1
-
VMMXU1
3U
RESVMMXU1
Uo
VSMSQI1
U1, U2, U0
FMMXU1
f
1MRS757054 A
IEC-ANSI
81LSH (1)
81LSH (2)
81LSH (3)
81LSH (4)
81LSH (5)
I <-> O CB
I <-> O DC (1)
I <-> O DC (2)
I <-> O DC (3)
I <-> O ES
25
TCM (1)
TCM (2)
-
3U
Vn
U1, U2, U0
f
Connector pins
X110-1,2
X110-3,4
X110-5,6
X110-7,6
X110-8,9
X110-10,9
X110-11,12
X110-13,12
REU615
Application Manual

Advertisement

Table of Contents
loading

Table of Contents