Section 3
REU615 standard configurations
3.4.3.2
38
In this standard configuration two restore stages are implemented. Depending on
input and output usage, it is possible to take other stages into use as well. The
operation signal is connected to the alarm LED 6.
GUID-ACA8588C-03FB-4389-B559-92CB612C6F8A V1 EN
Figure 17:
Arc protection
Arc protection (ARCSARC1...3) is included as an optional function.
The arc protection offers individual function blocks for three arc sensors that can
be connected to the IED. The arc protection in this standard configuration detects
an arc flash and supplies the information for the operating arc protection unit,
which de-energizes the faulty area by opening the circuit breaker. It is possible to
use, for example, fast GOOSE communication to route the detected information to
the circuit breaker.
The alarm LED 10 is used as a common arc detected indication.