ABB REU615 Applications Manual page 48

Voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

Section 3
REU615 standard configurations
42
GUID-1CF419D7-518A-431F-BCAB-02413BE39E22 V1 EN
Figure 21:
Disconnector position indication
The voltage transformer truck position indication is done with DCSXSWI1
function block. There are three disconnector status blocks (DCSXSWI1...3)
available in the IED. The remaining two not described in the functional diagram
are available in PCM600 for connection where applicable.
The binary inputs X110:5 and X110:6 are used for connection of voltage
transformer truck position. The inputs are connected to DCSXSWI1.
Table 13:
Device positions indicated by binary inputs 5 and 6
Primary device position
Busbar disconnector closed
Busbar disconnector open
Voltage transformer truck in service
position
Voltage transformer truck in test position
The binary inputs X110:7 and X110:8 are used for the position indication of the
busbar-side earth switch.
Input to be energized
Input 5 (X110:8-9)
x
x
1MRS757054 A
Input 6 (X110:10-9)
x
x
REU615
Application Manual