Functions - ABB REU615 Applications Manual

Voltage protection and control
Hide thumbs Also See for REU615:
Table of Contents

Advertisement

Section 3
REU615 standard configurations
3.5.2
44
phase non-directional overcurrent protection, three-phase under and overvoltage
protection. The IED also incorporates a thermal overload protection function,
which supervises the thermal stress of the transformer windings to prevent
premature aging of the winding's insulation.
The RTD/mA input module is optional in the standard configuration. When using
the RTD/mA input module it is possible to have the tap changer position indication
as an mA signal, ambient temperature of the power transformer can be used in
thermal protection and the multi-purpose protection functions are available. The
multi-purpose protection function enables protection based on analog values from
the IEDs RTD/mA input module, or from other IEDs using analog horizontal
GOOSE messaging.
The IED with a standard configuration is delivered from the factory with default
settings and parameters. The end-user flexibility for incoming, outgoing and
internal signal designation within the IED enables this configuration to be further
adapted to different primary circuit layouts and the related functionality needs by
modifying the internal functionality using PCM600.

Functions

Table 14:
Functions included in the standard configuration B
Functionality
Protection
Three-phase non-directional
overcurrent protection, low stage,
instance 1
Three-phase non-directional
overcurrent protection, high stage,
instance 1
Three-phase non-directional
overcurrent protection,
instantaneous stage, instance 1
Three-phase undervoltage
protection, instance 1
Three-phase undervoltage
protection, instance 2
Three-phase undervoltage
protection, instance 3
Three-phase overvoltage
protection, instance 1
Three-phase overvoltage
protection, instance 2
Three-phase overvoltage
protection, instance 3
Three-phase thermal overload
protection for power transformers,
two time constants
Master trip, instance 1
Table continues on next page
IEC 61850
IEC 60617
PHLPTOC1
3I> (1)
PHHPTOC1
3I>> (1)
PHIPTOC1
3I>>> (1)
PHPTUV1
3U< (1)
PHPTUV2
3U< (2)
PHPTUV3
3U< (3)
PHPTOV1
3U> (1)
PHPTOV2
3U> (2)
PHPTOV3
3U> (3)
T2PTTR1
3Ith>T
TRPPTRC1
Master Trip (1)
1MRS757054 A
IEC-ANSI
51P-1 (1)
51P-2 (1)
50P/51P (1)
27 (1)
27 (2)
27 (3)
59 (1)
59 (2)
59 (3)
49T
94/86 (1)
REU615