Maintenance; Notes On Safety For The Maintenance; Maintenance Programme - Riello RLAS 1000 EV Installation, Use And Maintenance Instructions

Dual fuel air atomizing oil/gas burner
Table of Contents

Advertisement

6

Maintenance

6.1

Notes on safety for the maintenance

The periodic maintenance is essential for the good operation, safe-
ty, yield and duration of the burner.
It allows you to reduce consumption and polluting emissions and to
keep the product in a reliable state over time.
The maintenance interventions and the calibration
of the burner must only be carried out by qualified,
authorised personnel, in accordance with the con-
tents of this manual and in compliance with the
DANGER
standards and regulations of current laws.
6.2

Maintenance programme

6.2.1
Maintenance frequency
The gas combustion system should be checked at
least once a year by a representative of the manu-
facturer or another specialised technician.
6.2.2
Safety test - with gas ball valve closed
It is fundamental to ensure the correct execution of the electrical
connections between the gas solenoid valves and the burner to
perform safely the commissioning.
For this purpose, after checking that the connections have been
carried out in accordance with the burner's electrical diagrams, an
ignition cycle with closed gas ball valve -dry test- must be per-
formed.
13 The manual ball gas valve must be closed
14 The electrical contacts of the burner limit switch need to be
closed
15 Ensures closed the contact of the low gas pressure switch
16 Make a trial for burner ignition
The start-up cycle must be as follows:
Starting the fan for pre-ventilation
Performing the gas valve seal control, if provided
Completion of pre-ventilation
Arrival of the ignition point
Power supply of the ignition transformer
Electrical Supply of solenoid gas valves
Since the manual gas ball valve is closed, the burner will not light
up and its control box will go to a safety lockout condition.
The actual electrical supply of the solenoid gas valves can be ver-
ified by inserting a tester. Some valves are equipped with light sig-
nals (or close/open position indicator) that turn on at the same time
as their power supply.
Maintenance
Before carrying out any maintenance, cleaning or checking opera-
tions:
Disconnect the electrical supply from the burner by
means of the main system switch.
DANGER
Close the fuel interception tap.
DANGER
Wait for the components in contact with heat sourc-
es to cool down completely.
IF THE ELECTRICAL SUPPLY OF THE GAS
VALVES OCCURS AT UNEXPECTED TIMES, DO
NOT OPEN MANUAL GAS BALL VALVE,
SWITCH OFF POWER LINE; CHECK THE
WARNING
WIRES; CORRECT THE ERRORS AND REPEAT
THE COMPLETE TEST.
6.2.3
Checking and cleaning
The operator must use the required equipment dur-
ing maintenance.
Combustion
Carry out an analysis of the combustion discharge gases.
Significant differences with respect to the previous check indicate
the points where more care should be exercised during mainte-
nance.
Combustion head
Open the burner and make sure that all components of the com-
bustion head are in good condition, not deformed by the high
temperatures, free of impurities from the surroundings and cor-
rectly positioned.
Fan
Check to make sure that no dust has accumulated inside the fan or
on its blades, as this condition will cause a reduction in the air flow
rate and provoke polluting combustion.
43
GB
20146383

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rlas 1200 ev20164347-2016434820164351-20164352

Table of Contents