6.2.5
Electrical panel maintenance
Turn off the burner's power supply using the main
system switch.
DANGER
In the event of maintenance/replacement of components in the low-
er part of the electrical panel, access is possible via the front of the
panel itself, following the directions below:
 unscrew the screws 2)(Fig. 55) of the control panel 1);
 extract the control panel and turn it 90°, hooking it with the
brackets in the profile of the electrical panel 1);
 after performing the operation, install the control panel1) in the
electrical panel with the appropriate screws 2), arranging the
cables present.
Failure to install the control panel in the seat of the
electrical panel, results in the machine's loss of "IP"
protection.
WARNING
1
6.2.6
Speed sensor adjustment
To calibrate the speed sensor 1)(Fig. 55), proceed as follows:
 loosen the screws 3);
 place the sensor on the disc blade 2), referring to the gradu-
ated scale 4);
 move backward the speed sensor 1) of one notch, according
to the distance from the disc blade of
Key (Fig. 55)
1
Speed sensor
2
Disk
3
Screw
4
Graduated scale
Maintenance
2
20110478
Fig. 54
5
/
inch.
64
45
GB
2
1
1
20110477
Fig. 55
20083150
Fig. 56
20146383