C2Prot
COM2 PROTOCOL
Defines the usage mode of the COM2 serial port:
Selectable values:
None: Serial communication disabled
Contin: Continuous transmission of the weight string. Can be used, among other things, to drive a
weight repeater. See the relevant section for details.
on deM: A weight string is transmitted when the operator presses the relevant front key or via Input2.
The command is only executed if weight is stable. Weight should vary by at least 20 divisions
between two subsequent transmissions.
Autom: A weight string is automatically transmitted when weight stabilizes on a value above
minimum weighing (20 divisions).
Slave: ASCII Protocol. See the relevant section for details.
Modbus: MODBUS RTU protocol. See the relevant section for details.
Default: Slave
C2bAud.
COM2 BAUD RATE
Defines the baud rate of the COM2 serial port.
The value should be set to the same value as the PC/PLC or the remote display.
Selectable values:
1200; 2400; 4800; 9600; 19200; 38400; 57600; 115200
Default: 9600
C2FrAN
COM2 PROTOCOL
Frame type. In case of SLAVE or MODBUS protocol, the 7-bit (E-7-1 and O-7-1) data format cannot be
selected:
Selectable values:
n-8-1; n-8-2; E-7-2; E-8-1; o-7-2; o-8-1
Default: n-8-1
Page 29