Download Print this page

Pepperl+Fuchs Hoffman 1001A Series Installation & Operation Manual page 7

Type y or z pressurization / purging kits
Hide thumbs Also See for Hoffman 1001A Series:

Advertisement

1/2"
pRotECtIVE
Gas sUpplY
HEaDER
Description
tubing or pipe Diameter
Maximum tubing / pipe length and
Maximum number of Bends / Elbows
1/2"
pRotECtIVE
Gas sUpplY
HEaDER
a
to ensure adequate protective gas flow to the protected enclosure(s), all piping and tubing must be fully
reamed.
precautions must be taken to prevent crimping and other damage to protective gas piping and tubing.
Determining Enclosure Inlet & outlet Connection locations
InlEt
Connections for Heavier than
Air Gases and Vapors
RSPSupply - 1-888-532-2706 - www.RSPSupply.com
http://www.RSPSupply.com/p-6798-Hoffman-A1001YZUMC2-Purging-Pressurization-System-10-CF.aspx
Getting started
Establishing Connection sizes, lengths & Bends
tYpICal sInGlE pRotECtED EnClosURE ConnECtIons
C
REFEREnCE
EnClosURE
pRotECtIon
sYstEM
sUpplY
a
B
a
system
supply tubing
1/4" O.D. Tubing
Fully Reamed
Fully Reamed
20 Feet
10 Bends
tYpICal MUltIplE pRotECtED EnClosURE ConnECtIons
B
sUpplY
EnClosURE
pRotECtIon
sYstEM
REFEREnCE
HElpFUl HInts
oUtlEt
InlEt
Connections for Lighter than
Air Gases and Vapors
EnClosURE pRotECtIon VEnt
pRotECtED
EnClosURE
C
B
Enclosure
Enclosure
Reference
supply
1/4" O.D. Tubing
1/4" O.D. Tubing
Fully Reamed
Fully Reamed
5 Feet
20 Feet
5 Bends
10 Bends
D
pRotECtED
pRotECtED
EnClosURE
EnClosURE
C
If flammable gases are lighter than air, the inlet con-
nection to each enclosure must enter near a bot-
tom corner. the outlet connection, for an optional
oUtlEt
enclosure protection vent or piping to an adjacent
protected enclosure, must exit near an extreme op-
posite top corner.
If flammable gases are heavier than air, inlet and outlet
connections must be reversed.
In all cases, the most prevalent gas must determine
the location of inlet and outlet connections.
(Optional)
E
D
Multi - Enclosure
optional Remote
Connections
1/2" I.D. Pipe
Fully Reamed
10 Feet
5 Elbows
D
pRotECtED
EnClosURE
HElpFUl HInts
E
Venting
1/2" I.D. Pipe
Fully Reamed
30 Feet
5 Elbows
7 7