Failure And Replacement Of Profibus Dp Cables - Siemens SIMATIC PCS 7 CPU 410-5H System Manual

Process control system / process automation
Table of Contents

Advertisement

Failure and replacement of components during redundant operation
11.2 Failure and replacement of components of the distributed I/Os
11.2.4

Failure and replacement of PROFIBUS DP cables

Starting situation
Failure
The S7-400H is in redundant system mode and
the PROFIBUS DP cable is defective.
Replacement procedure
Proceed as follows to replace PROFIBUS DP cables:
Step
1
2
198
What to do?
Check the cabling and localize the
interrupted PROFIBUS DP cable.
Replace the defective cable.
How does the system react?
With single-channel one-sided I/O:
Rack failure OB (OB 86) is started (incoming
event). The DP master can no longer process
connected DP slaves
(station failure).
The LED BUS1F flashes.
With switched I/O:
I/O redundancy error OB (OB 70) is started
(incoming event). DP slaves are addressed
via the DP master of the partner.
The LED BUS1F and the LED REDF are
flashing.
How does the system react?
The CPUs process the error OBs synchronized
with each other
With one-sided I/O:
Rack failure OB 86 (outgoing event)
The LED BUS1F goes out.
The DP slaves can be addressed via the
DP master system.
With switched I/O:
I/O redundancy error OB 70 (outgoing
event).
The DP slaves can be addressed via both
DP master systems.
The LED BUS1F and the LED REDF go
out.
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB