Determining The Monitoring Times - Siemens SIMATIC PCS 7 CPU 410-5H System Manual

Process control system / process automation
Table of Contents

Advertisement

Link-up and update
8.3 Time monitoring
8.3.2

Determining the monitoring times

Calculation using STEP 7 or formulas
STEP 7 automatically calculates the monitoring times listed below for each new
configuration. You can also calculate these times using the formulas and procedures
described below. They are equivalent to the formulas provided in STEP 7.
● Maximum cycle time extension
● Maximum communication delay
● Maximum inhibit time for priority classes
● Minimum I/O retention time
You can also start automatic calculation of monitoring times with Properties CPU > H
Parameters in HW Config.
Monitoring time accuracy
Note
The monitoring times determined by STEP 7 or by using formulas merely represent
recommended values.
These times are based on a fault-tolerant system with two communication peers and an
average communication load.
Your system profile may differ considerably from those scenarios, therefore the following
rules must be observed.
● A high communication load can significantly increase cycle time.
● Any modification of the system in operation may lead to a significant increase in cycle
times.
● Any increase in the number of programs executed in priority classes > 15 (in particular
processing of communication blocks) increases the delay in communication and extends
the cycle time.
● You can even undercut the calculated monitoring times in small plants with high-
performance requirements.
126
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB