Communication Via Point-To-Point Cp On The Et 200M - Siemens SIMATIC PCS 7 CPU 410-5H System Manual

Process control system / process automation
Table of Contents

Advertisement

Supplementary information
15.9 Communication via S7 connections
15.9.3

Communication via point-to-point CP on the ET 200M

Connection via ET 200M
Links from fault-tolerant systems to single-channel systems are often possible only by way of
point-to-point connections, as many systems offer no other connection options.
In order to make the data of a single-channel system available to CPUs of the fault-tolerant
system as well, the point-to-point CP, i.e., CP 341, must be installed in a distributed rack
along with two IM 153-2 modules.
Configuring connections
Redundant connections between the point-to-point CP and the fault-tolerant system are not
necessary.
Figure 15-13 Example of connecting a fault-tolerant system to a single-channel third-party system via
266
switched PROFIBUS DP
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB