Siemens SIMATIC PCS 7 CPU 410-5H System Manual page 303

Process control system / process automation
Table of Contents

Advertisement

Extended cycle time due to nested interrupts
Table 15- 14 Extended cycle time due to nested interrupts
CPU
Hardware
interrupt
CPU 410-5H
75 µs
stand-alone
mode
CPU 410-5H
180 µs
redundant
The program runtime at interrupt level must be added to this time extension.
If several interrupts are nested, their times must be added together.
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
Diagnostic
Time-of-
interrupt
day inter-
rupt
40 µs
50 µs
70 µs
200 µs
15.15 Cycle and response times of the CPU 410-5H
Delay interrupt
Cyclic
inter-
rupt
40 µs
40 µs
120 µs
120 µs
Supplementary information
Programming
I/O
error
access
error
20 µs
20 µs
90 µs
45 µs
Asyn-
chronous
error
55 µs