Starting situation
The fault-tolerant system is operating in redundant system mode.
Procedure
To edit the CPU parameters of a fault-tolerant system, follow the steps outlined below.
Details of each step are described in a subsection.
Step
What to do?
1
Editing CPU parameters offline
2
Stopping the reserve CPU
3
Downloading modified CPU parameters to the reserve
CPU
4
Switch to CPU with modified configuration
5
Transition to redundant system mode
Note
After changing the hardware configuration, download takes place practically automatically.
You then no longer have to perform the steps described in sections Step 2: Stopping the
reserve CPU (Page 176) to Step 5: Transition to redundant system mode (Page 179). The
system behavior remains as described.
You will find more information in the HW Config online help "Download to module ->
Download station configuration in RUN mode". You will find more information in the HW
Config online help "Download to module -> Download station configuration in RUN mode".
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB
System modifications during redundant operation
10.5 Editing CPU parameters
See section
Step 1: Editing CPU parameters offline
(Page 176)
Step 2: Stopping the reserve CPU (Page 176)
Step 3: Downloading a new hardware configura-
tion to the reserve CPU (Page 177)
Step 4: Switching to CPU with modified configura-
tion (Page 177)
Step 5: Transition to redundant system mode
(Page 179)
175