M-system R1MS-GH3 Instruction Manual page 7

Thermocouple & dc input module
Table of Contents

Advertisement

■ INPUT REGISTERS DESCRIPTION
(1) ANALOG INPUT IN ENGINEERING UNIT (30017 to 30032)
Indicates analog input values in engineering unit for each channel (1 – 8). The unit is specific to each input type: °C for
temperature, Volts for voltage. The data are 32-bit floating values, which requires two consecutive registers for one module.
(2) CHANNEL STATUS (30081 to 30088)
Indicates the current status of analog inputs (1 – 8). The following list shows the names and descriptions of each bit.
BIT
NAME
6
Input Overrange
7
ADC Error
12
Cold Junction Compensation SW
Others
Reserved
■ INPUT REGISTERS DESCRIPTION
Indicates I/O type for each channel. The data are 16-bit integer values.
MODEL
I/O
R1MS-GH3
DC input
R2M-2G3
R1M-GH2
DC input
R1M-GH2
T/C input
R1MS-GH3
R2M-2H3
R1M-J3
RTD input
POT input
R1M-D1
DO
R1M-A1
DI
DESCRIPTION
Indicates the designated analog input is in overrange, defined as one or more of
the following condition:
• ADC input value 0x0000 or 0xFFFF
• Burnout status for thermocouple input
• Out of range defined in the temperature table (thermocouple)
• ADC error
0 : Normal
1 : Overrange
Indicates the status of ADC.
0 : Normal
1 : Error
Indicates whether the cold junction compensation is enabled or disabled, for
thermocouple input.
0 : Disable
1 : Enable
For system's use
I/O TYPE
0x00
-10 to +10 V
0x00
-20 to +20 V
0x01
-5 to +5 V
0x02
-1 to +1 V
0x03
-800 to +800 mV
0x04
-200 to +200 mV
0x05
-50 to +50 mV
0x06
-10 to +10 mV
0x10
0x11
K (CA)
0x12
E (CRC)
0x13
J (IC)
0x14
T (CC)
0x15
B (RH)
0x16
R
0x17
S
0x18
C (WRe 5-26)
0x19
N
0x1A
U
0x1B
L
0x1C
P (Platinel II)
0x30
JPt 100 (JIS '89)
0x31
Pt 100 (JIS '89)
0x32
Pt 100 (JIS '97, IEC)
0x33
Pt 50 Ω (JIS '81)
0x34
Ni 508.4 Ω
0x35
Pt 1000
0x40
0 to 100 ohms
0x41
0 to 500 ohms
0x42
0 to 1 kohms
0x43
0 to 10 kohms
0x60
0x70
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SELECTION
USABLE RANGE
-10 to +10 V
-22.7 to +22.7 V
-5.6 to +5.6 V
-1.4 to +1.4 V
-860 to +860 mV
-215 to +215 mV
-53 to +53 mV
-13.4 to +13.4 mV
(PR)
0 to 1770°C
-270 to +1370°C
-270 to +1000°C
-210 to +1200°C
-270 to +400°C
100 to 1820°C
-50 to +1760°C
-50 to +1760°C
0 to 2320°C
-270 to +1300°C
-200 to +600°C
-200 to +900°C
0 to 1395°C
-200 to +500°C
-200 to +660°C
-200 to +850°C
-200 to +649°C
-50 to +280°C
-200 to +850°C
0 to 100 %
0 to 100 %
0 to 100 %
0 to 100 %
R1MS-GH3
NOTES
ATT SW ON
ATT SW ON
ATT SW ON
EM-5671 Rev.6 P. 7 / 8