13.5 Piping installation of R32

13.5.1
Pipe materials used and flaring
Copper pipes are used for refrigerant piping. Pipes
which comply with JIS Regulations need to be used.
Room air conditioners which use R410A and R32
have higher pressure; thus, using pipes which comply
with the Regulations is important.
The pipe thickness is regulated by revised JIS B 8607
"Flaring and brazing fittings for refrigerant" and the
pipe thickness for R410A, R32 is shown in the table.
Caution
For connection piping, use copper phosphate seamless pipes (1220T) as regulated in "JIS H 3300" and the pipe
thickness is 0.8 mm.
In the market, there are some pipes of 0.7 mm thickness, but do not use these pipes (0.8 mm thickness has to be
strictly followed).
It is recommended to use pipes whose adhesion amount of oil is at or less than 40 mg / 10 m.
At the same time, do not use pipes with dent, de-shape, and color change (especially inside).
13.5.2
Processing and connection of pipes
For refrigerant pipe installation, be aware of moisture and dirt do not get into the pipes, and make sure of no
refrigerant leakage.
◎ The procedure of flaring and precautions
a) Cutting of pipes:use pipe cutter and cut the pipe slowly not to de-shape the pipe.
b) Removal of burrs on the edge of pipe (reamer or scraper)
If the condition of pipe edge after the deburring is no good or if burrs attaches on the flaring, it may cause
refrigerant leakage. Turn the pipe end down and perform deburring carefully.
c) Insert the flare nut (use the nut which is a part of the CZ parts)
d) Flaring
Ensure the cleanliness of clump bar and pipe, and perform flaring carefully.
Use the existing flare tools or flare tools for R410A. Be aware that the sizes and dimensions of flaring is different
in each flaring tool. If you use the existing flaring tools, use flaring gauge to measure the length of the flaring part.
Dimensions "a" (mm)
Piping
size
Flare tools
(mm)
Clutch type
6.35 (1/4")
0.5 ~ 1.0
9.52 (3/8")
0.5 ~ 1.0
12.70 (1/2")
0.5 ~ 1.0
15.88 (5/8")
0.5 ~ 1.0
R22
Flare tools
for R410A
Wing nut
Clutch type Clutch type
type
1.0 ~ 1.5
0 ~ 0.5
1.0 ~ 1.5
1.0 ~ 1.5
0 ~ 0.5
1.0 ~ 1.5
1.5 ~ 2.0
0 ~ 0.5
1.0 ~ 1.5
1.5 ~ 2.0
0 ~ 0.5
1.0 ~ 1.5
Pipe thickness
O and OL materials
Diameter
1/4
3/8
1/2
5/8
Dimensions "a" (mm)
R410A/R32
Flare tools
Flare tools
for R410A
Wing nut
Clutch type
type
1.5 ~ 2.0
0 ~ 0.5
1.5 ~ 2.0
0 ~ 0.5
2.0 ~ 2.5
0 ~ 0.5
2.0 ~ 2.5
0 ~ 0.5
70
Thickness (mm)
Diameter
R410A
(mm)
6.35
9.52
12.70
15.88
Nut outer diameter (mm)
Bar
R32
R22
0.80
0.80
0.80
1.00
R410A
R22
R32
17
17
22
22
24
26
27
29