Example of manual valve addressing (Zoning
setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
Zoning control is connecting 2 or more indoor units at one pipe of HR
unit. In case of Zoning control, in order to set controls with multiple
indoor units connection uses the rotary switch. Namely, only the rotary
switch changes from same valve set condition and set indoor units
connection.
1
On DIP switch of the corresponding valves and sets the rotary
switch at 0.
2
Setting the number with tact switch.
3
In case of addition of indoor units to same port, increases 1 with the
rotary switch and sets number with tact switch.
4
In case of checking the number which the corresponding valve is
stored, turn on DIP switch and set the number of rotary switch.
5
Indoor units set available 7 per a port(rotary switch 0~6), in case of
setting above of 7 with rotary switch, it will display error.
6
Setting the rotary switch on original condition(HR unit number set
conditions) after all finishing a piping setting.
7
The rotary switch set value of above number of indoor units which
is connected with FF and prevents a malfunction.
(Example: The case where 3 indoor units is connected in piping 1,
sets from rotary switch 0,1,2 and 3,4,5 with FF set)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote
control.
No.
Display and setup
- Operation: None
7-SEG
SW01E
1
0
- Display: None
SW02B
SW01B
SW01C
- Operation : Turn dip S/W No.1 on to
address valve #1
7-SEG
SW01E
2
- Display : Existing value saved in
0
EEPROM is displayed in 7-SEG.
SW02B
SW01B
SW01C
- Operation : Set the digit of 10(1) to the
number in Group High data of the wired
remote control connected to the
corresponding indoor unit to the valve #1
7-SEG
SW01E
3
0
by pressing left tack S/W.
- Display : Digit increasing with the times
of pressing tack S/W is displayed in left
SW02B
SW01B
SW01C
7-SEG.
- Operation : SW01C : 1
7-SEG
SW01E
4
- Display : Display former value.
SW02B
SW01B
SW01C
- Operation : Setting No. using SW02B and
7-SEG
SW01E
SW01B, SW01C : 1
5
- Display : Display setting value.
SW02B
SW01B
SW01C
- Operation : Turn dip S/W No.1 off to save
the address of valve #1
7-SEG
SW01E
6
- Display : "11" displayed in 7-SEG
disappears.
SW02B
SW01B
SW01C
- Operation : Return valve of addressing
HR unit.
7-SEG
SW01E
7
0
- Display : None
SW02B
SW01B
SW01C
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be
addressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
Setup and Contents
Method of checking the pipe detection result
at HR unit
In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit
No.
Display and setup
- Operation: Turn DIP S/W No.1 on.
1
- Display: "11" is displayed in 7-SEG
7-SEG
SW01E
- Operation: Turn DIP S/W No.1 off
2
- 7-SEG disappeared
7-SEG
SW01E
Identification of Manual Valve ID (Address)
No.
Display and setup
- Operation: more than 2 DIP switches
turned on.
1
- Display: "Er" is displayed in 7-SEG
7-SEG
SW01E
Method of checking the pipe detection result
at outdoor unit
1
Wait for 5 minutes, after Pipe detection is completed.
2
Turn on the No.10,14,16 DIP S/W of SUB PCB at master unit
3
Check the data on 7- segment, switching rotary 01,02.
ROTARY 01 ROTARY 02

Setting method of Master indoor unit in zoning

1
Turn DIP switch 5,6,10 on at system off.
2
Set the left Rotary switch for HR unit.(Rotary switch No. "0" ' HR unit
No. "1")
3
Set the right Rotary switch for IDU unit.(Rotary switch No. "0" ' HR
unit branch No. "1")
4
Display the Master IDU No. of the HR unit on 7segment.(Default
display is "00" on 7segment)
5
Press the black button.(The IDU No. increase every 1 second in the
zoning )
6
Set the Master IDU.(Press the red button during 1.5 seconds stop
twinkling)
ROTARY 01 ROTARY 02
7 segment
CAUTION
!
• Waiting for 80 seconds after power on.
• The zoning information and Master IDU information remove from
EEPROM after Auto-addressing.
• If there is installed the central control, it is impossible setting of
Master IDU in zoning.
Setup and Contents
Setup and Contents
The connected port number of HR
unit
The connected HR unit number
The auto addressing number of indoor
unit (digit of 1)
The auto addressing number of indoor
unit (digit of 10)
No. of Indoor unit.
No. of HR unit branch.
No. of HR unit.