Setting Power Adjustment Parameters - Huawei SUN2000-50KTL-M0 User Manual

Hide thumbs Also See for SUN2000-50KTL-M0:
Table of Contents

Advertisement

SUN2000-(50KTL, 60KTL, 65KTL)-M0
User Manual
Parameter
HVRT compensation
power factor of
reactive power in
positive sequence
VRT exit hysteresis
threshold
Grid voltage
protection shield
during VRT
Active islanding
Soft start time after
grid failure (s)

7.2.2.4 Setting Power Adjustment Parameters

Procedure
Step 1 Choose Function Menu > Settings > Power Adjustment to access the settings
screen.
Issue 06 (2020-07-07)
Description
During HVRT, the inverter needs to
generate reactive power to support the
power grid. This parameter is used to
set the reactive power generated by
the inverter.
Specifies the LVRT/HVRT recovery
threshold.
Specifies whether to shield the
undervoltage protection function
during LVRT or HVRT.
Specifies whether to enable the active
islanding protection function.
Specifies the time for the power to
gradually increase when the SUN2000
restarts after the power grid recovers.
Copyright © Huawei Technologies Co., Ltd.
7 Man-Machine Interactions
Remarks
N/A
● This parameter is displayed
when LVRT or HVRT is set to
Enable.
● LVRT recovery threshold =
Threshold for triggering LVRT
+ VRT exit hysteresis threshold
● HVRT recovery threshold =
Threshold for triggering HVRT
+ VRT exit hysteresis threshold
This parameter is displayed when
LVRT or HVRT is set to Enable.
N/A
N/A