INSTALLATION INSTRUCTIONS AND OWNER'S HANDBOOK

CAUTION:
All gas burners MUST be installed by trained and licensed technicians.
WARNING:
Installation of this burner must conform with local codes requirements or, in the absence of local codes,
with the Standard: National Fuel Gas code ANSI Z223.1-1984, and CAN/CGA B149.1 & 2 AND UL 795.
If an external electrical source is utilized, the conversion burner, when installed, must be electrically
grounded in accordance with local codes or, in the absence of local codes, with the national Electrical
Code, ANSI/NFPA No. 70-1990 and CSA Electrical Code C22.2 No.0 M1982 & C22.2 No 3. 1988.
Authorities having jurisdiction should be consulted before installations are made. The owner is required
to retain this manual for future reference.
GAS SUPPLY PRESSURES
MANIFOLD PRESSURES
POWER
MOTOR
CONTROL MODULE
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing
property damage, personal injury or death.
Do not store or use gasoline or any other flammable vapours or liquid in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS:
1) Do not try to light any appliance.
2) Do not touch electrical switches; do not use any phone in your building.
3) Immediately call your gas supplier from a neighbour's phone.
Follow the gas supplier's instructions.
4) If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas
supplier.
3245
TECHNICAL SPECIFICATIONS
FIRING RATES:
HIGH 360,000 TO 900,000 Btu/hr
LOW 250,000 TO 490,000 Btu/hr
NATURAL GAS
HIGH FIRE
MIN. 7" wc
MAX. 14" wc
MIN. 2.3" wc
MAX. 3.3" wc
LOW FIRE
HIGH FIRE
MIN. 7" wc
MIN. 8" wc
MAX. 14" wc
MAX. 13" wc
MIN. 0.55" wc
MIN. 2.6" wc
MAX. 1.1" wc
MAX. 6.0" wc
120 Volts 60 Hz 1 phase
233T 4.3 Amps 3250 rpm 325 rad/s.
RMG 88.62
GB
PROPANE
LOW FIRE
MIN. 8" wc
MAX. 13" wc
MIN. 1.7" wc
MAX. 3.4" wc
2