Cisco Nexus 93360YC-FX2 Hardware Installation Manual page 28

Nx-os mode switch
Hide thumbs Also See for Nexus 93360YC-FX2:
Table of Contents

Advertisement

Installing the Chassis in a Two-Post Rack
Before you begin
• Make sure that the two-post rack is properly installed and secured to the concrete subfloor.
• Make sure that two center-mount brackets are securely fastened to the middle of each side of the chassis.
• Make sure that you have six customer-supplied rack-mount screws (typically M6 x 10 mm or the
• You have at least two people to install the chassis.
Warning
Statement 1006 Chassis Warning for Rack-Mounting and Servicing
To prevent bodily injury when mounting or servicing this unit in a rack, you must take special precautions to
ensure that the system remains stable. The following guidelines are provided to ensure your safety:
• This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
• When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the
• If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the
Step 1
Use one person to position the chassis so that it is near the top of the rack with the fan and power supply modules in the
appropriate aisle and the center-mount bracket has its screw holes aligned to screw holes on the two-post rack.
If these modules have a blue coloring for port-side exhaust airflow, then you must position the modules by the cold aisle.
If the modules have a burgundy coloring for port-side intake airflow, you must position the modules by the hot aisle.
Cisco Nexus 93360YC-FX2 NX-OS Mode Switch Hardware Installation Guide
20
appropriate screw for the vertical mounting rails on the rack).
heaviest component at the bottom of the rack.
unit in the rack.
Installing the Chassis