■[F_1] Input procedure of the Set value of instantaneous output
The Set point of the switch output can be set manually.
<Operation>
Press the
button in function selection mode to display [F_1]. (When OUT1 or OUT2 is assigned to be
accumulated output mode, [F_3] is displayed.)
Input of the Set point 1 (OUT1)
[n_1]
and the current Set value are displayed in turn.
Press the
and
referring to the list of outputs (page 21).
: When Non-Reverse output is selected as the switch operation, [P_1]
is displayed.
Input of the Set point 2 (OUT1)
[n_2]
and the current Set value are displayed in turn.
Press the
and
referring to the list of outputs (page 21).
: When Non-Reverse output is selected as the switch operation, [P_2]
is displayed.
Input of the Set point 3 (OUT2)
[n_3]
and the current Set value are displayed in turn.
Press the
and
referring to the list of outputs (page 21).
: When Non-Reverse output is selected as the switch operation, [P_3]
is displayed.
Input of the Set point 4 (OUT2)
[n_4]
and the current Set value are displayed in turn.
Press the
and
referring to the list of outputs (page 21).
: When Non-Reverse output is selected as the switch operation, [P_4]
is displayed.
[F_1] Input procedure of the Set value of instantaneous output is completed.
Press the
button to change the value
Press the
button to change the value
Press the
button to change the value
Press the
button to change the value
Press the
Return to measurement mode.