ELECTRICAL SYSTEM

ELECTRICAL SYSTEM
as set up by the
manufacturer
LAYOUT (A) - (B)
Burners RL 70/M - RL 100/M - RL 130/M
• Models RL 70-100-130/M leave the factory
preset for 380V power supply.
• If 220V power supply is used, change the
motor connection from star to delta and
change the setting of the thermal cut-out as
well.
Key to Layout (A) - (B)
CMV
- Motor contactor
LAL 1.25 - Control box
FR
- Photocell
MB
- Terminal strip
MV
- Fan motor
PO
- Oil pressure switch
RT
- Thermal cut-out
S1
- Switch for following operations :
MAN = manual
AUT = automatic
OFF
S2
- Button for :
-
= power reduction
+ = power increase
SM
- Servomotor
TA
- Ignition transformer
TB
- Burner ground (earth) connection
VM
- Delivery pump valve
VS
- Delivery pump valve (safety valve)
VS1
- Safety valve on return
VU
- Valve on nozzle return
ELECTRICAL CONNECTIONS
set by installer
Use flexible cables according to regulation EN
60 335-1:
• if in PVC boot, use at least HO5 VV-F
• if in rubber boot, use at least H05 RR-F.
All the cables to be connected to the burner ter-
minal strip 8)(B) must be routed through the fair-
leads.
The fairleads can be used in various ways. One
example is given below:
RL 70/M
1- Pg 13,5
Three-phase power supply
2- Pg 11
Single-phase power supply
3- Pg 11
Control device TL
4- Pg 9
Control
device
(RWF40)
5- Pg 9
Set up for faird lead
6- Pg 11
Set up for faird lead
7- Pg 13,5
Set up for faird lead
RL 100/M - RL 130/M
1- Pg 13,5
Three-phase power supply
2- Pg 11
Single-phase power supply
3- Pg 11
Control device TL
4- Pg 13,5
Control
device
(RWF40)
5- Pg 9
Set up for faird lead
6- Pg 11
Set up for faird lead
TR
or
probe
TR
or
probe