Advertisement

5. Arrange the bunches according to size from thickest to the thinnest between the E
5. Arrange the bunches according to size from thickest to the thinnest between the EMI
conductive cushions.
conductive cushions.
6. If more than one cable go through a grommet, seal the grommet by applying Loctite 5221
inside the grommet.
6. If more than one cable go through a grommet, seal the grommet by applying Locti
5221 (catalogue number 25551) inside the grommet.

Routing the control cables inside the cabinet

Use the existing trunking in the cabinet wherever possible. Use sleeving if cables are laid
Routing the control cables inside the cabinet
against sharp edges. When running cables to or from a swing-out frame, leave enough
Use the existing trunking in the cabinet wherever possible. Use sleeving if cables are l
slack at the hinge to allow the frame to open fully.
against sharp edges. When running cables to or from the swing-out frame, leave enou

Connecting control cabling

slack at the hinge to allow the frame to open fully.
Connect the conductors to the appropriate terminals. Refer to the wiring diagrams delivered
with the drive.
Connecting to the inverter control unit (A41)
Connect the inner twisted pair shields and all separate grounding wires to the grounding
Connect the conductors to the appropriate terminals (see page 127) of the control unit
clamps closest to the terminals.
terminal block X504 (option +L504).
The drawing below represents the grounding of the control cabling when connecting to a
Connect the inner twisted pair shields and all separate grounding wires to the groundin
terminal block inside the cabinet. The grounding is done in the same way when connecting
clamps below the control unit.
directly to a component such as the control unit.
The drawing below represents a drive with additional I/O terminal block (option +L504
Notes:
Without the block, the grounding is made the same way.
Notes:
Do not ground the outer shield of the cable here since it is grounded at the lead-
through.
Keep any signal wire pairs twisted as close to the terminals as possible. Twisting t
wire with its return wire reduces disturbances caused by inductive coupling.
Electrical installation
Electrical installation 43