98 Technical data
Tightening torques
Unless a tightening torque is specified in the text, the following torques can be used.
Electrical connections
■
Size
M3
M4
M5
M6
M8
M10
M12
M16
Mechanical connections
■
Size
M5
M6
M8
Insulation supports
■
Size
M6
M8
M10
M12
Cable lugs
■
Size
M8
M10
M12
Typical resistor cable sizes
This table gives copper cable types. Cable sizing is based on max. 9 cables laid on a cable
ladder side by side, three ladder type trays one on top of the other, ambient temperature
30 °C, PVC insulation, surface temperature 70 °C and 90 °C (EN 60204-1 and IEC
60364-5-2/2001). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive. I
current.
Torque
0.5 N·m (4.4 lbf·in)
1 N·m (9 lbf·in)
4 N·m (35 lbf·in)
9 N·m (6.6 lbf·ft)
22 N·m (16 lbf·ft)
42 N·m (31 lbf·ft)
70 N·m (52 lbf·ft)
120 N·m (90 lbf·ft)
Max. torque
6 N·m (53 lbf·in)
10 N·m (7.4 lbf·ft)
24 N·m (17.7 lbf·ft)
Max. torque
5 N·m (44 lbf·in)
9 N·m (6.6 lbf·ft)
18 N·m (13.3 lbf·ft)
31 N·m (23 lbf·ft)
Max. torque
15 N·m (11 lbf·ft)
32 N·m (23.5 lbf·ft)
50 N·m (37 lbf·ft)
Strength class
4.6...8.8
4.6...8.8
8.8
8.8
8.8
8.8
8.8
8.8
Strength class
8.8
8.8
8.8
Strength class
8.8
8.8
8.8
8.8
Strength class
8.8
8.8
8.8
is the dimensioning
rms dim