98 Technical data

Tightening torques

Unless a tightening torque is specified in the text, the following torques can be used.

Electrical connections

Size
M3
M4
M5
M6
M8
M10
M12
M16

Mechanical connections

Size
M5
M6
M8

Insulation supports

Size
M6
M8
M10
M12

Cable lugs

Size
M8
M10
M12

Typical resistor cable sizes

This table gives copper cable types. Cable sizing is based on max. 9 cables laid on a cable
ladder side by side, three ladder type trays one on top of the other, ambient temperature
30 °C, PVC insulation, surface temperature 70 °C and 90 °C (EN 60204-1 and IEC
60364-5-2/2001). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive. I
current.
Torque
0.5 N·m (4.4 lbf·in)
1 N·m (9 lbf·in)
4 N·m (35 lbf·in)
9 N·m (6.6 lbf·ft)
22 N·m (16 lbf·ft)
42 N·m (31 lbf·ft)
70 N·m (52 lbf·ft)
120 N·m (90 lbf·ft)
Max. torque
6 N·m (53 lbf·in)
10 N·m (7.4 lbf·ft)
24 N·m (17.7 lbf·ft)
Max. torque
5 N·m (44 lbf·in)
9 N·m (6.6 lbf·ft)
18 N·m (13.3 lbf·ft)
31 N·m (23 lbf·ft)
Max. torque
15 N·m (11 lbf·ft)
32 N·m (23.5 lbf·ft)
50 N·m (37 lbf·ft)
Strength class
4.6...8.8
4.6...8.8
8.8
8.8
8.8
8.8
8.8
8.8
Strength class
8.8
8.8
8.8
Strength class
8.8
8.8
8.8
8.8
Strength class
8.8
8.8
8.8
is the dimensioning
rms dim