Riello LMV5 Series Commissioning Instructions page 57

Display and settings
Hide thumbs Also See for LMV5 Series:

Advertisement

Analog output to
the VSD X73-4
Quick shutdown in the
event of great speed
deviations during
operation
Speed feedback signal
Speed input
X70
This output is used for delivering the preselected speed setpoint to the VSD.
Current:
Output load:
Resolution:
Cross-sectional area of wire:
This function is used to trigger safety shutdown as quickly as possible (within about 1
second) if great speed deviations are detected, or if speed = 0 is detected in operation.
This check is made from phase Ignition On 38 through Afterburn time 70.
The degree of deviation where quick shutdown shall take place can be set via parame-
ter TolQuickShutdown:
Checking is deactivated when 100 % is entered as the tolerance value.
Setting range:
0...100 %
Resolution:
0.4 %
Parameter
TolQuickShutdown
The motor's speed can be acquired with different types of sensors. To detect the mo-
tor's direction of rotation with a sensor, a sensor disk with angular steps of 60°, 120°
and 180° is used. The sensor disk generates pulse intervals of different length.
Speed acquisition is safety-related!
We recommend using the accessory set AGG5.310.
To enable the acquired speed to be standardized to the range of 0...100 %, the speed
that corresponds to 100 % must be parameterized (
Motor speed:
100 % speed:
Sensor:
Power supply:
Switching current:
Cable length:
0 / 4...20 mA
0...105 % (
max. 750
(burden), short-circuit-proof
0.1 %
2
0.1 mm
300...6300 1 / min
1350...6300 1/ min
Inductive sensor to DIN 19234 or open collector (pnp)
U
< 4 V, U
> DC 15 V
CEsat
CEmin
DC 10 V, max. 15 mA
> 10 mA
max. 100 m (sensor line must be run separately !)
55
«Standardization of Speed»)
«Standardization of speed»).