Burner identification
(burner ID)
Burner ID offers the OEM the opportunity - which may also be the OEM's duty - to store
an individual burner ID in each LMV5... system by means of the OEM password, prior
to delivery. The burner ID can be entered here, for example.
Burner ID is then used to enable or disable the data transfer between the ba-
sic unit and the AZL5... backup storage. Parameters can be loaded to the
AZL5... at any time, if the burner ID in the basic unit is not in the «as sup-
plied» status.
Saving the parameter from AZL5... in the basic unit is only possible, if the burner ID is
the same as in the AZL5... and in the basic unit or the burner ID of basic unit is still in
the delivery status.
The burner ID itself is part of the data transfer in both directions (if that is possible).
In addition, for the burner, the burner ID represents one of a number of start prerequi-
sites. In other words, the burner cannot be started up as long as the burner ID is in the
«as supplied» status.
So, it is possible to have data transmission between the basic unit and the AZL5... of
one plant (burner IDs are identical) and between an AZL5... and a new basic unit
(burner ID «as supplied» by Siemens).
Data transmission between AZL5... and basic units of different plants (burner IDs not
identical) is not possible (no «cloning»!).