4. Setting gas valve proving
Menu level 1
Menu level 2
Params & Display
BurnerControl
5. Addressing the
actuators
Menu level 1
Menu level 2
Params & Display
Actuators
Menu level 3
ValveProving
Selection of gas valve proving: No VP, VP startup, VP shutdown or VP stup/shd
(
«Gas valve proving system»)
Prior to programming the actuators, the connector for the bus connection at the last
CAN bus element must be plugged in.
Menu level 3
Addressing
For addressing an actuator, select the respective type of actuator:
1. Air actuator
2. Gas actuator (oil) [for dual-fuel burners with only one fuel actuator]
3. Oil actuator
4. Auxiliary actuator
5. Auxiliary actuator 2
6. Auxiliary actuator 3
Confirm by pressing Enter (
The AZL5... prompts you to operate the addressing switch on the actuator.
Menu level 4
Menu level 5
ValveProvingType
Menu level 4
Menu level 5
1. AirActuator
2. GasActuat(Oil)
3. OilActuator
4. AuxActuator
5. AuxActuator 2
6. AuxActuator 3
«Display and operating unit AZL5...»).
33
Menu level 6
Menu level 6
5921