Riello LMV5 Series Commissioning Instructions page 26

Display and settings
Hide thumbs Also See for LMV5 Series:

Advertisement

5921
90°
Pos.
0 %
7550d09e/0704
Change of load / position with several points
Using this method, up to 15 points can be defined.
6. Shutdown
On the menu: «Params & Display»
«Special Positions»
or on:
«Manual Operation»
and confirm
7. Setting the postpurge positions
The system shuts down and stops in phase «Driving to postpurge 72».
Now, the postpurge positions on menu «Special positions» can be set.
Then, on «Program Stop», set to «deactivated».
The system continues the shutdown sequence and stops in phase «Standby 12».
24
AIR
FUEL
AUX
100 %
Load
«Ratio Control»
«Settings Gas / Oil»
«Autom / Manual / Off»
«Autom / Manual / Off» to «Burner off»