Mitsubishi Electric MELSEC iQ-F Series Quick Start Manual page 31

Safety extension module
Hide thumbs Also See for MELSEC iQ-F Series:
Table of Contents

Advertisement

7 CPU MODULE SETTINGS
Communication
Parameter Settings
Settings
4
Click the [Parameter + Program] button, and click the
5
Click the OK button.
6
When the data is written to the programmable controller, power OFF the FX5U CPU module and the safety
main module, and then power them ON simultaneously (within two seconds).
An error will occur if only the FX5U CPU module is reset or either one of the FX5U CPU module or
the safety extension module is powered OFF and ON.
Point
Make sure to power ON the FX5U CPU module and the safety main module simultaneously (within
two seconds).
Writing Data to the
Programmable Controller
OFF
button.
Execute
ON
7
8
9
31

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-f fx5Melsec iq-f fx5u

Table of Contents