Shutting Down The Ups - Huawei UPS2000-A Series User Manual

Table of Contents

Advertisement

UPS2000-A-(6 kVA-10 kVA)
User Manual
Step 10 Ensure that the UPS runs properly, close the UPS AC output circuit breaker, and AC output
circuit breaker on the rear panel of the UPS (only for professional version) to start the loads.
----End

5.2.2 Shutting down the UPS

Shutting down the Inverter to Transfer the UPS to Bypass Mode
To shut down the inverter, perform any of the following operations:
Shutting down the Inverter to Transfer the UPS to No Output State
Step 1 Shut down the loads.
Step 2 Perform "shutdown operations" on the UPS. The inverter shuts down, and the UPS transfers
to bypass mode.
Step 3 Open the UPS upstream AC input circuit breaker, AC output circuit breaker on the rear panel
of the UPS, and output circuit breaker. After all indicators turn off and fans stop, the UPS
shuts down, and the loads power off.
Issue 05 (2019-12-19)
To prevent triggering overload protection, start the loads with higher power and then loads with lower
power.
On the default screen, hold down ESC for more than 5 seconds. Release the button when
you hear a beep sound. The inverter shuts down, and the UPS transfers to bypass mode.
On the default screen, press
down the inverter. The UPS transfers to bypass mode, as shown in
Figure 5-17 Shutting down the inverter
The two methods are called "shutdown operations" in this section.
Copyright © Huawei Technologies Co., Ltd.
to enter the CTR menu. Choose INV OFF to shut
5 Operations
Figure
5-17.
88