UPS2000-A-(6 kVA-10 kVA)
User Manual
Alarm
Alarm
Name
Identifier
(Alarm ID)
WebUI
Decimal
System
Remainin
22-1
g cap.
warning
Issue 05 (2019-12-19)
Alarm
Alarm
Identifier
level
(Alarm ID)
LCD
Heuristicim
al System
34-1
Minor
Copyright © Huawei Technologies Co., Ltd.
Alarm
Impact on
Clear
the System
Mode
lifespan is
affected.
Automatic
If no action is
clear
taken,
continued
discharge will
result in
system
shutdown due
to EOD.
B Alarm Handling
Repair Proposal
number of batteries.
Measure: Check that
the configured
number of batteries
is consistent with the
actual number.
Possible cause: The
actual number of
batteries does not
meet requirements.
Measure: Check that
the actual number of
batteries meets
requirements.
Possible cause: The
charger is abnormal.
Measure: Check that
the charger voltage
is normal
immediately after
the batteries are
disconnected.
Possible cause: The
battery discharge
lasts too long.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
mains input is
abnormal.
Measure: Check the
mains, and charge
batteries in a timely
manner.
Possible cause: The
number of batteries
or battery capacity is
incorrectly set.
Measure: Check the
configured battery
capacity.