B.E.G. LUXOMAT PD4-M-DIM-Corridor Installation And Operating Instruction

B.E.G. LUXOMAT PD4-M-DIM-Corridor Installation And Operating Instruction

Occupancy detectors

Advertisement

Quick Links

LUXOMAT
Installation and Operating Instruction for
1. Mounting preparations
Work on the 230 V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled
electrical personnel in accordance
with electrical regulations.
Disconnect supply before installing!
The device is not suited for safe
disconnection of the mains supply.
When in Master/Slave mode of op-
eration, the Master-appliance must
always be installed at the location
where there is least daylight.
3. Position DIP-switches
Surface mounting
False ceiling mounting
Light
measure-
ment
2
1
3
OFF
ON
VA
HA
LED
COR
OFF
ON
DIP
4. DIP switch functions
DIP-
ON
OFF
switch
1
Semi automatic mode
Fully automatic mode
2
LED OFF
LED ON
3
Corridor mode
Standard mode
The DIP settings are enabled again by
• Adjusting the DIP switches when closed
• Reset with test sun setting at the potentiometers
• Reset when open
Corridor function: After deactivation by an external push button, the
detector switches off and returns to automatic mode after 5 sec.
Function LEDs OFF: In the open state and in test mode, the LEDs are
always ON.
7. Option:
Resetting when-
open: Deletes all
values set with
the remote con-
trol, light OFF.
IR-PDim
Wall bracket for remote
control IR-PDim
®
B.E.G.-Occupancy detectors
2a. Installation of the LUXOMAT
ATTENTION: For maximum sensitivity the detec-
tor-, lens- and corridor-axis must match.
opened
closed
b
Light
measurement
The DIP switch set-
tings are overriden
using the remote
control.
2
1
3
DIP
OFF
ON
OFF
ON
1
DIP
2
3
8. Settings by remote control
50
to
1500
Lux
Lux
or
or
1
30
to
min
min
max
max
ON
ON
OFF
OFF
1
to
60
min
min
50
t < 5 sec.
1500
Lux
Lux
max
PD4-M-DIM- Corridor
PD4-DIM-C-SM
®
open
close
The detector must be in stalled on a solid and level
surface. The circular cover ring must be removed
prior to assembly. To do this, twist the lens (C) an-
ticlockwise through approximately 5° and lift off.
Having connected up the wires in accordance
with regulations, secure the detector with 2
screws. After installation replace the lens and
lock (turn clockwise). Mains to be connected.
5. Putting into operation / Settings
Initialization
In the first 60 seconds after connecting the power supply the LUXOMAT
PD4-M-DIM-C will go through a self test cycle. During this time the device
doesn´t respond to movement, but will stay on the status depending on the
selected initialization mode on or off (INI OFF or ON).
120 60 50
A
Warning: In the Ini-OFF mode, does not switch on lights at power start
40
!
up. After 60 seconds, detector would switch on lights on upon detecting
30
15
movement.
5
10
Follow-up time for light control
25 22
30
The time can be set infinitely variably at between
18
16 10
R1
16
5
1 and 30 minutes.
10
2
6
TEST
3
Symbol TEST: Test mode (Every movement switches on the
1
1
TEST
30
15
light for a period of 1 second, switching it off for a period of
2 seconds after that regardless of the level of brightness)
Twilight-switch for light control (relay 1)
2000
The switch-on value for the light can be set at between 10
1200
600
and 2000 Lux. Using the rotary control, the luminance set
200
points can be set as desired.
40
Symbol
:
Night-time operation
Symbol
: Daytime /Night-time operation
Orientation lighting
ON
60
This rotary controller serves to determine the working time of
50
30
the orientation lighting (fixed to 20 %).
10
5
"ON" for permanent orientation lighting.
OFF
"OFF" for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses
9s
2s
sent to the master. The setting can be made with activated (
) or deactivated ( ) LED indicator.
LED ON
For devices with a separate slave input, 2 sec. can be set.
LED OFF
Unlocking device - Activation of
the programming mode
Luminance set point for
constant light control
max
Start of the dim process
Stop of the dim process and reading
ON
in the current light value as new
luminance set point
OFF
50
1500
Lux
Lux
Follow-up time light
50
1500
Lux
Lux
Fully automatic/semi automatic
mode => (see page 2, point10)
Orientation lighting ON/OFF
20 % of the nominal light
Orientation lighting and its
max
follow-up time
Preset/user mode
ON
=> (see page 2, point11 )
Locking device – Exit programming
OFF
mode
LED fl ashes
Permanent protection against
sabotage
PD4-M-DIM-C-SM/-FC
2b. Montage LUXOMAT
C
up the cables in accordance with regulations, the
detector is inserted into the opening as shown in the
drawing opposite and fixed into position with the
assistance of the spring clip.
6. Settings carried out using remote
control (optional)
®
1. Check Battery:
open battery compartment by pressing the
plastic springs together and removing the
battery-holder.
1
25 22
30
R1
TEST
1
2. IMPORTANT
Please pay attention, that the setting is
Potentio-meter 1 at "TEST" and Potentiometer
2 not at "SUN". All values which have
been programmed using the remote control
will be deleted in the event of power failure
in the position "TEST /SUN". Please switch
Potentiometer 2 over to "MOON" or any
other value.
Caution:
Settings with remote control supersede the
settings by courtesy of potentiometers.
9. Explanation of the remote control button functions
In the initialization period
During initialization phase/self test cycle
Lights can be set to on or off status during initialization(60 Seconds) by
using INI OFF/ON mode.
Light on / off when closed
=> (see page 2, point 12)
50
1500
Dimming in the closed state
Lux
Lux
=> (see page 2, point 11)
Test operation in the closed condition to enable
Disable the test mode: press reset
Resetting when closed
The lighting relay is switched off, i.e. opened and the follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illuminated). This
operating mode can only be activated during the period of 5 seconds after
pressing the "lock" button. This status will only permit actuating the function
t < 5 s
"Light on/Light off". The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 - 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Dim in the open state
50
1500
To set a target value, proceed as follows (example workplace):Place one lux
Lux
Lux
meter flat on the desk. Set the light with the help of remote control IR-PDim
by pressing the buttons „max" or „min" for starting the dim process. Wait
until the desired light level is reached.
50
1500
Confi rmation by the preset value
Lux
Lux
Light during the initialization
50
1500
max
The light is on by default in the initialization time.
Lux
Lux
On / off with the „Light" button during Initialization. The final condition is
then active.
max
ON
Follow-up time orientation light ON / OFF when open
Note: Also during the orientation phase of the light constant light control is
active: With sufficient brightness is <20% dimmed and turned off the lights if
ON
OFF
necessary.
GB
PD4-DIM-C-FC
®
68 mm
The detector has
been designed and
developed specifically
for installation in sus-
pended ceilings.
A circular opening
of diameter 68 mm
must first of all be
produced in the
ceiling.
Having connected
Remote control
LUXOMAT
IR-PDim
®
120 60 50
A
40
30
15
5
10
16 10
5
2
1
TEST
30
15
1
2
2
25 22
2000
30
2000
18
1200
18
1200
R1
16
16
600
600
10
10
200
6
6
200
TEST
3
3
1
40
40

Advertisement

loading
Need help?

Need help?

Do you have a question about the LUXOMAT PD4-M-DIM-Corridor and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for B.E.G. LUXOMAT PD4-M-DIM-Corridor

  • Page 1 LUXOMAT PD4-M-DIM- Corridor ® Installation and Operating Instruction for PD4-M-DIM-C-SM/-FC B.E.G.-Occupancy detectors 1. Mounting preparations 2a. Installation of the LUXOMAT PD4-DIM-C-SM 2b. Montage LUXOMAT PD4-DIM-C-FC ® ® Work on the 230 V mains supply ATTENTION: For maximum sensitivity the detec- 68 mm The detector has may only be carried out by quali-...
  • Page 2 10. Fully / Semi automatic mode 15. Wiring diagrams 18. Technical data PD4-M-DIM-C (for IR-PDim functions see page 1) Standard mode with master DIM occupancy detectors Sensor and power supply in one case Power supply: 230 V~ ±10 % The system switches over when the “Light” push-button is Power consumption: <...

This manual is also suitable for:

Luxomat pd4-m-dim-c-smLuxomat pd4-m-dim-c-fc