Table Of Factory's (Defaults) Parameters Settings - Whisper Power 12-2000 User Manual

Unit combining inverter, battery charger and transfer system
Hide thumbs Also See for 12-2000:
Table of Contents

Advertisement

10 TABLE OF RELEVANT FACTORY (DEFAULTS) PARAMETERS SETTINGS
No. of
config
1107
Maximum current of the AC source
1108
Under voltage of the empty battery
1109
Sub-voltage of the charged battery
1110
Restart voltage of the inverter after under voltage of the battery
1111
Automatic startup at power up
1112
Inverter frequency
1121
Maximum DC voltage for stopping the WPC
1126
Source assistance (Smart Boost) permitted
1127
Grid feeding allowed
1138
Battery charge current
1139
Battery voltage correction according to the temperature
1140
Battery maintenance voltage
1143
Voltage 1 to allow a new battery cycle
1144
Duration of under voltage 1 to allow a new cycle
1145
Voltage 2 to allow a new battery cycle
1146
Duration of under voltage 2 to allow a new cycle
1156
Battery absorption voltage
1157
Duration of absorption
1159
Current at end of absorption
1161
Minimum interval between absorptions
1167
Wave max. of the battery in charger mode (V/cell)
1187
Sensitivity of the charge detection (100% approx.25W)
1188
Number of pulse load research
1189
Time interval between load search pulses
1190
Duration of under voltage of battery before disconnection
1191
Dynamic compensation for under voltage
1194
Battery adaptive low voltage allowed
1195
Max voltage for adaptive low voltage
1198
Time elapsing before transfer relay opens
1199
AC in voltage causing the opening of the transfer relay
1200
Immediate open critical threshold for the transfer
1246
Auxiliary contact 1 activated by voltage 1 {1247} after delays {1248}
1247
Voltage 1under which auxiliary contact 1 is activated
1248
Delays on voltage 1 to activate auxiliary contact 1
1249
Auxiliary contact 1 activated by voltage 2 {1250} after delays {1251}
1250
Voltage 2 under which auxiliary contact 1 is activated
1251
Delays on voltage 2 to activate auxiliary contact 1
1252
Auxiliary contact 1 activated by voltage 3 {1253} after delays {1254}
1253
Voltage 3 under which auxiliary contact 1 is activated
1254
Delays on voltage 3 to activate auxiliary contact 1
1255
Voltage for deactivation of Aux 1
1256
Delays on voltage {1255} to deactivate auxiliary contact 1
1258
Auxiliary contact 1 activated by power 1
1259
Power 1 above which auxiliary contact 1 is activated
1260
Duration of power 1 for activating auxiliary contact 1
1261
Auxiliary contact 1 activated by power 2
1262
Power 2 above which auxiliary contact 1 is activated
1263
Duration of power 2 for activating auxiliary contact 1
1
Setting NC=Factory not changeable
February 2020/ WPC / EN
Denomination / description
FACTORY SETTINGS
Units
Fact.
Mod.
value
value
A
16
V/cell
1.93
V/cell
1.75
V/cell
2
y/n
no
Hz
50/60
V/cell
2.84
y/n
yes
y/n
No
A
45
mV/°C/
-4
cell
V/cell
2.27
V/cell
2.1
min.
30
V/cell
2.05
sec.
60
V/cell
2.4
h
2
Adc
10
h
2
Vdc
0.5
NC
1
%
10
--
1
sec.
0.8
min.
3
y/n
Yes
o/n
no
V/cell
2.08
sec.
8
Vac
180/90
Vac
110/55
y/n
yes
V/cell
1.97
min.
1
y/n
Yes
V/cell
2
min.
10
y/n
Yes
V/cell
2.03
min.
60
V/cell
2.27
min.
120
y/n
yes
%
70
min.
15
y/n
yes
%
100
min.
5
35