General Rules, Notes And Definitions; Validation Of The Safety Functions; Competence; Validation Procedure - ABB ACS880 Series User Manual

Atex-certified motor thermal protection functions for cabinet-built drives
Hide thumbs Also See for ACS880 Series:
Table of Contents

Advertisement

62 Technical data
Protection degree
Installation in
Mechanical specifications
Dimensions (Height ×
Width × Depth)
Weight
Weight including 4501
Terminals
Vibration
Approvals
• ATEX Ex II (1) G D
• IECEx
• EAC Ex
• SIL 2 certified according to IEC 61508
For the complete list of approvals, see the relay data sheet.
Isolation data
Isolation voltage
For the complete relay technical data, see www.prelectronics.com.

General rules, notes and definitions

Validation of the safety functions

You must do an acceptance test (validation) to validate the correct operation of safety
functions.

Competence

The acceptance test of the safety function must be carried out by a competent person with
expertise and knowledge of the safety function as well as functional safety, as required by
IEC 61508-1 clause 6, and ATEX/Ex regulations. The test procedures and report must be
documented and signed by this person.

Validation procedure

You must do the acceptance test using the checklist given in section Start-up and acceptance
test:
at initial start-up of the safety function
after any changes related to the safety function (wiring, components,
safety-function-related parameter settings, etc.)
after any maintenance work related to the safety function.
The acceptance test must include at least the following steps:
you must have an acceptance test plan
you must test all commissioned functions for proper operation, from each operation
location
Without 4501
With 4501
Wire size
Tightening torque
2 ... 13.2 Hz
13.2 ... 100 Hz
Test/working: Input to any
Analog output to supply
Status relay to supply
IP20
Pollution degree 2 & meas. / overvoltage cat. II
109 × 23.5 × 104 mm
109 × 23.5 × 116 mm
approximately 185 g
approximately 200 g
2
0.13 ... 2.08 mm
(AWG 26 ... 14) stranded wire
0.5 N·m (4.4 lbf·in)
±1 mm
±0.7 g
2.6 kV AC / 300 V AC reinforced isolation
2.6 kV AC / 300 V AC reinforced isolation
1.5 kV AC / 150 V AC reinforced isolation

Hide quick links: