60 Technical data
Input
Analog Output
Signalling LEDs
Environmental conditions
Operating
Storage
General
Mounting
Dimensions (Height × Width × Depth)
Weight
Terminal connection
Protection class
Approvals
• ATEX Ex II (1) G D
• IECEx
• TUV Certificate No. C-IS-236198-02, SIL 2 according to IEC 61511
• DNV A-13778 and KR MIL20769-EL001 Certificates for maritime applications
For the complete list of approvals, see the relay data sheet.
Isolation data
Isolation voltage (Test
voltage)
For the complete relay technical data, see www.gminternational.com.
■
PR electronics 9116B1 universal converter
Ordering information
Universal converter - Uo 28 V DC (max. loop voltage)
Display / Programming front (not included in the ABB
delivery)
Calibration and linearity
accuracy
Temperature influence
Calibration accuracy
Linearity error
Supply voltage influence
Load influence
Temperature influence
PWR
BURN
A
B
In/Outs
In/Supply
Analog Out/Supply
Analog Out/Alarm Outs
Alarm Outs/Supply
Alarm Out/Alarm Out
≤ ± 40 μV on mV or thermocouple, 200 mohm on RTD,
0.2% on potentiometer or ± 0.05% of input value
≤ ± 2 μV, 20 mohm, 0.02% or ± 0.01% of input value
for a 1 °C change.
≤ ± 0.1% of full scale
≤ ± 0.05% of full scale
≤ ± 0.05% of full scale for a min to max supply change
≤ ± 0.05% of full scale for a 0...100% load resistance
change
≤ ± 0.01% on zero and span for a 1 °C change
Power supply indication (green)
Burnout (red)
Alarm A (red)
Alarm B (red)
Temperature limits -20 °C ... +60 °C (-4 °F ... +140 °F),
relative humidity max. 90% non condensing, up to 35 °C
(95 °F).
Temperature limits -45 °C ... +80 °C (-49 °F ... +176 °F)
T35 DIN Rail according to EN 50022
114.5 × 22.5 × 99 mm
approximately 160 g
Screw terminal blocks, max. 2.5 mm
IP20
1.5 kV
1.5 kV
500 V
1.5 kV
1.5 kV
1.5 kV
9116B1
4501
2