Specifications - Infinite TRANSTECTOR 700 AV/T Series Owner's Manual

60 k(i) power conditioner with voltage regulation (60 hz)
Table of Contents

Advertisement

Quadruple Output Power Conditioner | Owners Manual
SPECIFICATIONS - 60K(I)
1.0 SCOPE
This specification covers the electrical characteristics of the 60 K(I) Power Conditioner which provides
clean regulated power for Varian On Board Imager™ or peripherals.
2.0 GENERAL
The Power Line Conditioner consists of an all copper, multiple tapped, triple shield isolation transformer.
The low output impedance of the transformer in conjunction with the electrostatic shields assures
precision hospital grade performance with excellent noise and transient attenuation. Independently
controlled inverse parallel electronic switches for each of the 7 taps per phase provide tight regulation
over a wide input range. Linear devices are used for line synchronization to prevent phase shift errors
normally associated with simple CT zero current crossing acquisition. The microprocessor control
accurately selects the correct tap to maintain the output no greater than +2.0 % of nominal, correcting
for voltage disturbances within one cycle. Digital processing technique provides fast and accurate
regulation without output voltage over or undershoot.
2.0.1 MODEL NUMBERS
MODEL INPUT VOLTAGE OUTPUT VOLTAGE
Model
8BNX-60KI-700AV/T
8CNX-60KI-700AV/T
8DNX-60KI-700AV/T
8ENX-60KI-700AV/T
2.1 AGENCIES
2.1.1 STANDARDS
The systems shall be designed in accordance with:
ƒ American National Standards Institute
ƒ Institute of Electrical and Electronic Engineers
ƒ National Electric Code (NEC)
ƒ National Fire Protection Association (NFPA Article 70)
ƒ UL 1449, 1012
ƒ FCC Article 15, Section J, Class A
ƒ ISO 9001
|
/v
Input Voltage
208 volts nominal input
240 volts nominal input
480 volts nominal input
600 volts nominal input
Output Voltages
480.277 volts output
480/277 volts output
480/277 volts output
480/277 volts output