Troubleshooting - Infinite TRANSTECTOR 700 AV/T Series Owner's Manual

60 k(i) power conditioner with voltage regulation (60 hz)
Table of Contents

Advertisement

Quadruple Output Power Conditioner | Owners Manual
TROUBLESHOOTING (continued)
TROUBLESHOOTING CONTINUED
6. Turn main AC on. With DC voltmeter on the millivolt scale check between TP1 and TP GND of
the control card and adjust pot P2 so meter reads "0" millivolts or close as possible.
Turn main AC on. With DC voltmeter on the millivolt scale check between TP1 and TP GND of the
control card and adjust pot P2 so meter reads "0" millivolts or close as possible.
NOTE: Refer to Appendix A Page 40 for test points and pot locations on control card.
7. Use the following formula to calculate the next adjustments. You must calculate each input
NOTE: Refer to Appendix A Page A51 for test points and pot locations on control card.
phase for each control card or a total of 3 calculations.
Use the following formula to calculate the next adjustments. You must calculate each input phase for
A. For phase 1 control card measure AC input at Line 1 to Line 2.
each control card or a total of 3 calculations.
B. For phase 2 control card measure AC input at Line 2 to Line 3.
A.
For phase 1 control card measure AC input at Line 1 to Line 2.
C. For phase 3 control card measure AC input at Line 1 to Line 3.
B.
For phase 2 control card measure AC input at Line 2 to Line 3.
FORMULA
C.
For phase 3 control card measure AC input at Line 1 to Line 3.
Example:
FORMULA
Actual AC Input x 2.47
480 (Nominal)
475 Volts AC Input x 2.47
480 (Nominal)
After calculations are complete, place DC voltmeter on the 20 volt scale and check between TP2 and TP
GND on control card. Adjust pot P1 so meter reads DC level calculated in Step 7 for all three phases.
8. After calculations are complete, place DC voltmeter on the 20 volt scale and check between
NOTE: If adjustments in Steps 6 and 7 are not possible, replace control card # 414921 and repeat Steps
TP2 and TP GND on control card. Adjust pot P1 so meter reads DC level calculated in Step 7
6 and 8.
for all three phases.
NOTE: Be sure to turn power off when replacing circuit boards.
NOTE: If adjustments in Steps 6 and 7 are not possible, replace control card #414921 and
repeat Steps 6 and 8.
NOTE: Be sure AC input is stable when making this adjustment. If the input changes, you must
re-calculate.
NOTE: Be sure to turn power off when replacing circuit boards.
NOTE: Output voltage correction is a "stepped correction", adjusting P1 will not cause a smooth change
NOTE: Be sure AC input is stable when making this adjustment. If the input changes, you
in output voltage as it is adjusted.
must re-calculate.
Turn the unit off. Plug in TB2 Molex connectors to all the control cards #414921.
NOTE: Output voltage correction is a "stepped correction", adjusting P1 will not cause a
smooth change in output voltage as it is adjusted.
Replace connectors K1 and K2 on over/under detect #35867.
9. Turn the unit off. Plug in TB2 Molex connectors to all the control cards #414921.
NOTE: P1 pot turned clockwise = decrease in output voltage and counter-clockwise = increase in output
10. Replace connectors K1 and K2 on over/under detect #35867.
voltage. By changing this adjustment on phase1 you may see the output voltage change from
line to neutral on two phases. It is best to use procedures in Steps 1 – 9 adjusting.
NOTE: P1 pot turned clockwise = decrease in output voltage and counter-clockwise =
increase in output voltage. By changing this adjustment on phase1 you may see the output
voltage change from line to neutral on two phases. It is best to use procedures in Steps 1 – 9
adjusting.
|
/v
= Volts DC at TP2
= 2.44 Volts DC at TP2
PAGE 33
26